Voltage Drop Calculator

Last updated: 2026-08-10

Use the Voltage Drop Calculator to get instant, accurate results. Enter your values below.
Inputs
Technical Parameters
Dimensions
Result
Enter values and press Calculate
Common Sizes — Click to Fill
Circuit length (m) Cable section (mm²) (mm²) Current (A) (A)
Alumbrado (1.5 mm²) 15 m 1.5 mm² 8 A
Tomas salón (2.5 mm²) 25 m 2.5 mm² 16 A
Electrodomésticos (4 mm²) 30 m 4 mm² 25 A
Climatización (6 mm²) 40 m 6 mm² 32 A
Subcuadro exterior (10 mm²) 55 m 10 mm² 40 A

When designing or troubleshooting an electrical installation, ensuring that the voltage at the end of a cable run remains within safe and functional limits is critical. Our Voltage Drop Calculator helps you quickly determine the expected voltage loss in a cable based on its length, cross-section, current, and system voltage, using the standard formula for copper conductors. This tool is essential for electricians, engineers, and DIY enthusiasts who need to verify compliance with regulations and avoid undersized cables.

What the Voltage Drop Calculator Does and When to Use It

The calculator solves for the voltage drop (in volts and as a percentage) across a two-wire copper cable circuit. It uses the fundamental DC resistance formula adapted for AC power distribution, assuming a resistive load and a conductor temperature typical for standard installations. The primary output is the percentage drop relative to the supply voltage, which is then checked against a common 3% threshold for branch circuits.

You should use this calculator whenever you are sizing cables for fixed installations, such as:

Formula Explained Variable by Variable

The calculator applies the following formula to compute the voltage drop:

dV = (2 × L × I) / (σ × S)

Where:

After calculating dV, the percentage drop is found by: dV_pct = (dV / V) × 100, where V is the system voltage (tension_v, default 230V). The tool then returns "SI" (Yes) if dV_pct is 3% or less, and "NO (>3%)" if it exceeds the limit.

Two Worked Examples with Concrete Numbers

Example 1: Garden Lighting Circuit

Scenario: You are installing a 30-meter run of cable from a 230V supply to power four 50W LED floodlights (total 200W, roughly 0.87A). You plan to use 1.5 mm² cable.

Inputs:

Calculation:
dV = (2 × 30 × 0.87) / (56 × 1.5) = 52.2 / 84 = 0.62 V
dV_pct = (0.62 / 230) × 100 = 0.27%

Result: The voltage drop is only 0.27%, well under the 3% limit. The 1.5 mm² cable is more than adequate for this load.

Example 2: Heavy Equipment in a Workshop

Scenario: A 7.5 kW single-phase motor (32A at 230V) needs to be supplied from a distribution board 45 meters away. You are considering 6 mm² cable.

Inputs:

Calculation:
dV = (2 × 45 × 32) / (56 × 6) = 2880 / 336 = 8.57 V
dV_pct = (8.57 / 230) × 100 = 3.73%

Result: The voltage drop of 3.73% exceeds the 3% limit. The calculator would return "NO (>3%)". To fix this, you would need to increase the cable size to 10 mm² or reduce the circuit length.

Common Mistakes When Using the Calculator

Even with a simple tool, users often make errors that lead to incorrect results. Avoid these pitfalls:

Frequently Asked Questions

Q1: Why does the formula multiply the length by 2?

A: The factor of 2 accounts for the total circuit length. In a single-phase system, the current flows out through the live wire and returns through the neutral (or the second live wire in a 230V system). Both conductors contribute to the voltage drop. If you only enter the one-way distance, the doubling ensures the calculation reflects the actual round-trip resistance.

Q2: My installation uses 12V DC. Can I still use this calculator?

A: Yes, you can, but with caution. The formula works for DC and AC circuits. However, the 3% pass/fail threshold is typically designed for AC mains voltage (230V/120V). For 12V systems, a 3% drop (0.36V) is extremely tight, and the cable would need to be very thick. For low-voltage systems, a 5% or 10% drop is often acceptable. Simply enter your system voltage and disregard the "Cumple REBT" warning; instead, focus on the absolute voltage drop value.

Q3: What should I do if the calculator says "NO (>3%)"?

A: The most common solution is to increase the cross-sectional area of the cable (use a thicker wire). Other approaches include:

Re-enter the new parameters until you achieve a passing result.

Written and reviewed by the CalcToWork editorial team. Last updated: 2026-08-10.